No.
(Addr.
Hex)
Name Description
Analog Output
Level
Unit
U5-05
(7D2)
PI Differential Feedback
PI Feedback 2
Displays the second PI feedback value if differential feedback is used
(H3-oo = 16).
10 V: 100% 0.01%
U5-06
(7D3)
PI Adjusted Feedback
PI Diff Fdbk
Displays the difference of both feedback values if differential feedback is
used (U5-01 - U5-05).
If differential feedback is not used, then U5-01 and U5-06 will be the same.
10 V: 100% 0.01%
U5-30
(3000)
Time Hr Min HHMM
Time Hr Min HHMM
Displays the current time (Hours and Minutes).
No signal output
available
1
U5-31
(3001)
Date Year
Date Year
Displays the current year.
No signal output
available
1
U5-32
(3002)
Date Mo Day MMDD
Date Mo Day MMDD
Displays the current date (Month and Day).
No signal output
available
1
U5-33
(3003)
Date Week 000W
Date Week
Displays the current date of the week.
0: Sunday
0: Sunday
1: Monday
1: Monday
2: Tuesday
2: Tuesday
3: Wednesday
3: Wednesday
4: Thursday
4: Thursday
5: Friday
5: Friday
6: Saturday
6: Saturday
No signal output
available
1
u
U6: Operation Status Monitors
No.
(Addr.
Hex)
Name Description
Analog Output
Level
Unit
U6-80 to
U6-83
(07B0 to
07B3)
Online IP Address IP Address currently available; U6-80 is the most significant octet.
No signal output
available.
-
U6-84 to
U6-87
(07B4 to
07B7)
Online IP Address Subnet currently available; U6-84 is the most significant octet.
No signal output
available.
-
U6-88 to
U6-91
(07B8 to
07F1)
Online Gateway Gateway currently available; U6-88 is the most significant octet.
No signal output
available.
-
U6-92
(07F2)
Online Gateway Link Speed
10: 10 Mbps
100: 100 Mbps
.
-
U6-93
(07F3)
Online Gateway Duplex Setting
0: Half
1: Full
.
-
U6-98
(07F8)
Online Gateway First Option Fault - -
U6-99
(07F9)
Current Fault Current Option Fault - -
Note: Available in bypass controller software versions VST800400 and later.
B.13 U: Monitors
346
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual