EasyManua.ls Logo

YASKAWA Z1000 - Z4: Bypass Control Option Boards

YASKAWA Z1000
466 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
u
Z4: Bypass Control Option Boards
No.
(Addr.
Hex)
Name Description Values Page
Z4-01
(8700)
IP Address 1
Sets the most significant octet of network static IP address.
Default: 192
Range: 0 to 255
217
Z4-02
(8701)
IP Address 2
Sets the second most significant octet of network static IP address.
Default: 168
Range: 0 to 255
217
Z4-03
(8702)
IP Address 3
Sets the third most significant octet of network static IP address.
Default: 1
Range: 0 to 255
217
Z4-04
(8703)
IP Address 4
Sets the fourth most significant octet of network static IP address.
Default: 20
Range: 0 to 255
217
Z4-05
(8704)
Subnet Mask 1
Sets the most significant octet of network static subnet mask.
Default: 255
Range: 0 to 255
217
Z4-06
(8705)
Subnet Mask 2
Sets the second most significant octet of network static subnet mask.
Default: 255
Range: 0 to 255
217
Z4-07
(8706)
Subnet Mask 3
Sets the third most significant octet of network static subnet mask.
Default: 255
Range: 0 to 255
217
Z4-08
(8707)
Subnet Mask 4
Sets the fourth most significant octet of network static subnet mask.
Default: 0
Range: 0 to 255
217
Z4-09
(8708)
Gateway IP Address 1
Sets the most significant octet of network gateway address.
Default: 192
Range: 0 to 255
218
Z4-10
(8709)
Gateway IP Address 2
Sets the second most significant octet of network gateway address.
Default: 168
Range: 0 to 255
218
Z4-11
(870A)
Gateway IP Address 3
Sets the third most significant octet of network gateway address.
Default: 1
Range: 0 to 255
218
Z4-12
(870B)
Gateway IP Address 4
Sets the fourth most significant octet of network gateway address.
Default: 1
Range: 0 to 255
218
Z4-13
(870C)
IP Address Mode Select
0: User-Defined (Static IP)
1: BOOTP
2: DHCP
Default: 2
Range: 0 to 2
218
Z4-14
(870D)
Duplex Select
0: Forced Half Duplex
1: Auto Negotiate Duplex Mode and Communication Speed
2: Forced Full Duplex
Default: 1
Range: 0 to 2
218
Z4-15
(870E)
Speed Mode Setting
10: 10 Mbps
100: 100 Mbps
Default: 10
Range: 10, 100
218
Z4-16
(870F)
Communication Loss
Timeout
Control connection timeout value for detection of communication loss.
Default: 0 s
Min.: 0
Max.: 300
218
Z4-17
(8710)
Ethernet Speed Scale
AC/DC Drive Object, Instance 1, Attribute 22
Default: 0
Min.: -15
Max.: 15
218
B.14 Z: Bypass Parameters
354
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual