YASKAWA Z1000 - Metasys N2 Binary Output (BO) Summary

YASKAWA Z1000
466 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Object ID Object Name Default Off (0) State On (1) State
BI 10 Multi-Function Output 7 (Z2-23) 0 Off On
BI 11 Multi-Function Output 8 (Z2-24) 0 Off On
BI 12 Multi-Function Output 9 (Z2-25) 0 Off On
BI 13 Safety Interlock Monitor 0 Safety Clear Safety Set
BI 14 HAND/AUTO Reference Monitor 0 AUTO or OFF HAND
BI 15 Multi-Function Input 3 Monitor 0 Off On
BI 16 Multi-Function Input 4 Monitor 0 Off On
BI 17 Multi-Function Input 5 Monitor 0 Off On
BI 18 Multi-Function Input 6 Monitor 0 Off On
BI 19 Multi-Function Input 7 Monitor 0 Off On
u
Metasys N2 Binary Output (BO) Summary
Table F.8 Metasys N2 Binary Output Summary (Bypass to Metasys N2)
Object ID Object Name Default Off (0) State On (1) State
BO 1 Run Forward Command 0 Stop Forward
BO 2 Run Reverse Command 0 Stop Reverse
BO 3 External Fault (EFB) Command 0 No Fault Fault (EFB)
BO 4 Fault Reset Command 0 No Reset Reset
BO 5
<1>
Multi-Function Input 3 (Z2-03) 0 Off On
BO 6
<1>
Multi-Function Input 4 (Z2-04) 0 Off On
BO 7
<1>
Multi-Function Input 5 (Z2-05) 0 Off On
BO 8
<1>
Multi-Function Input 6 (Z2-06) 0 Off On
BO 9
<1>
Multi-Function Input 7 (Z2-07) 0 Off On
BO10
Panel Lock
Note: Not supported
0
BO 11 Communication Fault Enable 0 FB14 Not Activated if Cable Loss Occurs FB14 Activated if Cable Loss Occurs
<1> Disabled when Z3-12 is set to 0 in bypass controller software versions VST800298 and later.
F.6 Metasys N2 Point Database
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
437