YASKAWA Z1000 - H3: Multi-Function Analog Inputs

YASKAWA Z1000
466 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
H2 Multi-Function Digital Output Settings
H2-oo
Setting
Function LCD Display Description Page
37 During frequency output During RUN 2
Open: Either the drive has stopped or baseblock, DC Injection Braking, or Initial
Excitation is being performed.
Closed: Drive is running the motor (not in a baseblock state and DC Injection is
not being performed).
159
39 Watt hour pulse output Watt-hour Pulse
Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate
the kWh count.
160
3D During speed search During SpdSrch Closed: Speed Search is being executed. 160
4C During fast stop During Fast Stop
Closed: A Fast Stop command has been entered from the operator or input
terminals.
160
4D oH Pre-alarm time limit OH Pre-Alarm Closed: oH pre-alarm time limit has passed. 160
60
Internal cooling fan
alarm
Fan Alrm Det
Closed: Internal cooling fan alarm
160
100 to
160
Function 0 to 60 with
inverse output
Note: A prefix of "!" is
added to represent
inverse functions on the
LCD keypad display.
Example: “!Zero speed”
Inverts the output switching of the multi-function output functions.
Set the last two digits of 1oo to reverse the output signal of that specific function.
160
u
H3: Multi-Function Analog Inputs
No.
(Addr.
Hex)
Name Description Values Page
H3-01
(410)
Terminal A1 Signal Level
Selection
Term A1 Level
0: 0 to 10 V with zero limit
0: 0-10V, (LowLim=0)
1: 0 to 10 V without zero limit
1: 0-10V, (BipolRef)
2: 4-20 mA
3: 0-20 mA
Note: Use jumper switch S1 to set input terminal A1 for current or
voltage.
Default: 0
Range: 0 to 3
160
H3-02
(434)
Terminal A1 Function
Selection
Term A1 FuncSel
Sets the function of terminal A1.
Default: 0
Range: 0 to 26
161
H3-03
(411)
Terminal A1 Gain Setting
Terminal A1 Gain
Sets the level of the input value selected in H3-02 when 10 V is input at
terminal A1.
Default: 100.0%
Min.: -999.9
Max.: 999.9
161
H3-04
(412)
Terminal A1 Bias Setting
Terminal A1 Bias
Sets the level of the input value selected in H3-02 when 0 V is input at terminal
A1.
Default: 0.0%
Min.: -999.9
Max.: 999.9
161
H3-09
(417)
Terminal A2 Signal Level
Selection
Term A2 Level
0: 0 to 10 V with zero limit
0: 0-10V, (LowLim=0)
1: 0 to 10 V without zero limit
1: 0-10V, (BipolRef)
2: 4 to 20 mA
2: 4-20 mA
3: 0 to 20 mA
3: 0-20 mA
Note: Use jumper switch S1 to set input terminal A2 for current or
voltage input signal.
Default: 2
Range: 0 to 3
162
H3-10
(418)
Terminal A2 Function
Selection
Term A2 FuncSel
Sets the function of terminal A2.
Default: 0
Range: 0 to 26
162
H3-11
(419)
Terminal A2 Gain Setting
Terminal A2 Gain
Sets the level of the input value selected in H3-10 when 10 V (20 mA) is input
at terminal A2.
Default: 100.0%
Min.: -999.9
Max.: 999.9
162
H3-12
(41A)
Terminal A2 Bias Setting
Terminal A2 Bias
Sets the level of the input value selected in H3-10 when 0 V (0 or 4 mA) is
input at terminal A2.
Default: 0.0%
Min.: -999.9
Max.: 999.9
162
H3-13
(41B)
Analog Input Filter Time
Constant
A1/A2 Filter T
Sets a primary delay filter time constant for terminals A1 and A2. Used for
noise filtering.
Default: 0.03 s
Min.: 0.00
Max.: 2.00
162
B.8 H Parameters: Multi-Function Terminals
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
325
B
Parameter List

Table of Contents