F.6 Metasys N2 Point Database
This section describes the Metasys N2 point database. This database features 100 logical points: 38 Analog Inputs (AI), 32
Analog Outputs (AO), 19 Binary Inputs (BI) and 11 Binary Outputs (BO). These points configure, control, and monitor the
operation of the drive.
u
Metasys N2 Analog Input (AI) Summary
Table F.5 Metasys N2 Analog Input Summary (Bypass to Metasys N2)
Object ID Object Name Units Bypass Parameter
AI 1 Speed Reference 0.01 Hz U1-01
AI 2 Output Speed 0.01 Hz U1-02
AI 3 Output Current 0.1 A U1-03/UB-01 in Drive/Bypass Mode
AI 4 kWatt Hour Meter kWh U4-10
AI 5 Output Power 0.1 kWh U1-08
AI 6 Drive Temperature
1 °C
U4-08 Will only report accurately when drive is
running.
AI 7 PI Feedback 0.01% U5-01
AI 8 AC Output Voltage 0.1 Vac U1-06
AI 9 DC Bus Voltage 1 Vdc U1-07
AI 10 Fault Code U2-01/UB-09. Reads UB-09 first and if 0 returns U2-01
AI 11 Elapsed Time - Hours 1 hour U4-01
AI 12 Elapsed Time - 10K Hours 10K hours U4-01
AI 13 MWatt Hour meter MWh U4-11
AI 14 Drive Rated Current A n9-01
AI 15 Communication Error Code Not supported. Always returns 0
AI 16 PI Deviation 0.01% U5-02
AI 17 PI Output Capacity 0.01% U5-03
AI 18 PI Reference 0.01% U5-04
AI 19 Last Fault Code U2-02
AI 20 Freq Ref @ Fault 0.01 Hz U2-03
AI 21 Output Freq @ Fault 0.01 Hz U2-04
AI 22 Output Current @ Fault 0.1 A U2-05
AI 23 Out Volt Ref @ Fault 0.1 Vac U2-07
AI 24 DC Bus Volts @ Fault 1 Vdc U2-08
AI 25 Output Power @ Fault 0.1 kW U2-09
AI 26 Input Term Status @ Fault U2-11
AI 27 Output Term Status @ Fault U2-12
AI 28 Operation Status @ Fault U2-13
AI 29 Elapsed Operation Time @ Fault 1 hour U2-14
AI 30 Most Recent Fault U3-01
AI 31 2nd Most Recent Fault U3-02
AI 32 3rd Most Recent Fault U3-03
AI 33 4th Most Recent Fault U3-04
AI 34 Elapsed Time @ Current Fault 1 hour U3-11
AI 35 Elapsed Time @ 2nd Fault 1 hour U3-12
AI 36 Elapsed Time @ 3rd Fault 1 hour U3-13
AI 37 Elapsed Time @ 4th Fault 1 hour U3-14
AI 38 Read Parameter Data