Binary Input Objects
Table C.7 Binary Input Objects
Object ID Object Name
Modbus
Address
Active Text Inactive Text PV Access
BI1 Input Terminal 1 002BH:bit 0 ON OFF R
BI2 Input Terminal 2 002BH:bit 1 ON OFF R
BI3 Input Terminal 3 002BH:bit 2 ON OFF R
BI4 Input Terminal 4 002BH:bit 3 ON OFF R
BI5 Input Terminal 5 002BH:bit 4 ON OFF R
BI6 Input Terminal 6 002BH:bit 5 ON OFF R
BI7 Input Terminal 7 002BH:bit 6 ON OFF R
BI8 Multi-Function Out 1 0020H:bit 5 ON OFF R
BI9 Multi-Function Out 2 0020H:bit 6 ON OFF R
BI10 BYP DI-1 STAT 8781H: bit 0 ON OFF R
BI11 BYP DI-2 STAT 8781H: bit 1 ON OFF R
BI12 BYP DI-3 STAT 8781H: bit 2 ON OFF R
BI13 BYP DI-4 STAT 8781H: bit 3 ON OFF R
BI14 BYP DI-5 STAT 8781H: bit 4 ON OFF R
BI15 BYP DI-6 STAT 8781H: bit 5 ON OFF R
BI16 BYP DI-7 STAT 8781H: bit 6 ON OFF R
BI17 BYP DI-8 STAT 8781H: bit 7 ON OFF R
BI18 BYP DO-1 STAT 8782H: bit 0 ON OFF R
BI19 BYP DO-2 STAT 8782H: bit 1 ON OFF R
BI20 BYP DO-3 STAT 8782H: bit 2 ON OFF R
BI21 BYP DO-4 STAT 8782H: bit 3 ON OFF R
BI22 BYP DO-5 STAT 8782H: bit 4 ON OFF R
BI23 BYP DO-6 STAT 8782H: bit 5 ON OFF R
BI24 BYP DO-7 STAT 8782H: bit 6 ON OFF R
BI25 BYP DO-8 STAT 8782H: bit 7 ON OFF R
BI26 BYP DO-9 STAT 8783H: bit 0 ON OFF R
BI27 BYP DO-10 STAT 8783H: bit 1 ON OFF R
BI28
<1>
Drive Fault Status 004BH: bit 7 FAULT OK R
BI29
<1>
Drive Alarm Status 004BH: bit 6 ALARM OK R
BI30
<1>
Drive or Bypass Alarm 8748H: bit 8 ALARM OK R
<1> Available in bypass controller software versions VST800400 and later.
u
Binary Output Objects
Table C.8 Binary Output Objects
Object ID Object Name
Modbus
Address
Active Text Inactive Text PV Access
BO1 MF Output M1-M2 0009H:bit 0 ON OFF C
BO2 MF Output M3-M4 0009H:bit 1 ON OFF C
BO3 MF Output M5-M6 0009H:bit 2 ON OFF C
BO4 Ref Sel: PI Setpoint 000FH:bit 1 ON OFF C
BO5 Ref Sel: Term S5 IN 8480H:bit 8 ON OFF C
BO6 Ref Sel: Term S6 IN 8480H:bit 9 ON OFF C
BO7 Refl Sel: Term S7 IN 8480H:bit 10 ON OFF C
BO8 BYP DO-07 COMMAND 8403H:bit 6 ON OFF C
BO9 BYP DO-08 COMMAND 8403H:bit 7 ON OFF C
B010 BYP DO-09 COMMAND 8403H:bit 8 ON OFF C
C.6 BACnet Objects Supported
370
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual