Object ID Object Name
Modbus
Address
Precision Range Units PV Access
AV13 Output Power 0047H
XXXX.X
(for drives rated
above 11 kVA)
XXX.XX
(for drives rated
11 kVA or
lower)
– kW R
AV14 Torque Reference (U1-09) 0048H XXXX.X – % R
AV15 MF Input Status 002BH – – – R
AV16 Drive Status 2 002CH – – – R
AV17 MF Output Status 002DH – – – R
AV18 DC Bus Voltage 0031H XXXXX – Volts R
AV19 PI Feedback Level 0038H XXXX.X – % R
AV20 PI Input Level 0039H XXXX.X – % R
AV21 PI Output Level 003AH XXXX.X – % R
AV22 Drive SW Num 004DH XXXXX – – R
AV23 Bypass SW Num 8791H XXXXX – – R
AV24 Comm Error Detail 003DH – – – R
AV25 KVA Setting 003EH XXXXX – – R
AV26 Control Method 0043H XXXXX – – R
AV27 Accel Time 0200H XXXX.X 0.0 to 6000.0 Sec W
AV28 Decel Time 0201H XXXX.X 0.0 to 6000.0 Sec W
AV29
<1>
Parameter Number – XXXXX 0 to FFFFH – W
AV30
<1>
Parameter Data – XXXXX 0 to FFFFH – W
AV31 Motor Current 8780H XXXX.X – Amps R
AV32 120 V to Kx Coils 8790H XXXXX – Volts R
AV33
<2>
Drive kWH
0x005C and
0x005D
XXXXXXX.X 0.0 to 32767999.9 kWH R
AV35
<3>
Drive Run Time 0x004C XXXX - Hours R
AV36
<3>
Output Freq In % 0x003F XXX.XX - % R
AV37
<3>
Output Freq In RPM 0x003E XXXX - RPM R
AV38
<3>
Torque Iq (U6-01) 0x0051 XXX.X - % R
AV39
<3>
Drive HOA Status
0x07DA first
digit
X - - R
AV40
<3>
Last Drive Fault
<4>
0x0081 XX.XX - - R
AV41
<3>
Last Bypass Fault
<5>
0x878C XXXX - - R
AV41
<3>
Last Bypass Fault 0x878C XXXX - - R
AV42
<3>
Fault Code
<6>
0080H (Drive
Fault)
or
8788H (Bypass
Fault)
XXXXX - - R
<1> Refer to Accessing Bypass Parameters and the Enter Command on page 374 for an explanation of how to read and write drive parameters not
listed in the analog or binary objects.
<2> Available in bypass controller software versions VST800298 and later.
<3> Available in bypass controller software versions VST800400 and later.
<4> Refer to Fault Trace Contents on page 402 for details.
<5> Bypass fault is reported by its fault number. Example: This object will report a value of 3 when an FB03 - External Fault Bypass is present.
<6> Drive faults report the drive fault code. Refer to Fault Trace Contents on page 402 for details. Bypass faults report the bypass fault number +
10000. For example: This object will report a value of 10003 when an FB03 - External Fault Bypass is present.
C.6 BACnet Objects Supported
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
369
C
BACnet
Communications