D.2 Communication Specifications
MEMOBUS/Modbus specifications appear in the following table:
Item Specifications
Interface RS-485
Communications Cycle Asynchronous (Start-stop synchronization)
Communication
Parameters
Communication Speeds
Available
1200, 2400, 4800, 9600, 19200, 38400, 57600, 76800, 115200 bps
Data length 8-bit (fixed)
Parity Select even, odd, or none
Stop bit 1-bit (fixed)
Protocol MEMOBUS/Modbus (using RTU mode only)
Max Number of Slaves 31 bypasses
D.2 Communication Specifications
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual