Metasys N2 Analog Output (AO) Summary
Table F.6 Metasys N2 Analog Output Summary (Bypass to Metasys N2)
Object ID Object Name Units Default Value Bypass Parameter
AO 1 Speed Command 0.01 Hz
AO 2 Acceleration Time seconds 30.0 C1-01
AO 3 Deceleration Time seconds 30.0 C1-02
AO 4 PI Proportional Gain 2.00 b5-02
AO 5 PI Integral Time seconds 5.0 b5-03
AO 6 Stall Prevention Level – Run % 120 L3-06
AO 7 Stall Prevention Level – Accel % 120 L3-02
AO 8 Frequency Reference Selection 0 Z1-07
AO 9 Run Command Selection 1 Z1-08
AO 10 PI Mode Select 0 b5-01
AO 11 Frequency Command Upper Limit % of Max 100.0 d2-01
AO 12 Frequency Command Lower Limit % of Max 0.0 d2-02
AO 13 Motor Rated Current A Motor model dependent E2-01
AO 14 Jump Frequency 1 0.1 Hz 0.0 d3-01
AO 15 Jump Frequency 2 0.1 Hz 0.0 d3-02
AO 16 Jump Frequency 3 0.1 Hz 0.0 d3-03
AO 17 Jump Frequency Bandwidth 0.1 Hz 1.0 d3-04
AO 18 Number of Auto Restarts 0 L5-01
AO 19 Operator Display Mode 0 o1-03
AO 20 Power Loss Ride-Thru seconds Drive model dependent L2-02
AO 21 Cable Loss Timeout seconds 2.0 Z3-06
AO 22 Cable Loss Speed 0.01 Hz 0.00 Z3-10
AO 23 PI Integral Limit 0.1% 100.0 b5-04
AO 24 PI Upper Limit Value 0.1 100.0 b5-06
AO 25 PI Offset Adjustment 0.1 0.0 b5-07
AO 26 PI Primary Delay Time 0.01 0.00 b5-08
AO 27
PI Feedback Reference Missing
Detection Select
1 0 b5-12
AO 28
PI Feedback Reference Missing
Detection Level
1% 0 b5-13
AO 29
PI Feedback Reference Missing
Detection Time
0.1 s 1.0 b5-14
AO 30 Read Parameter Number
AO 31 Write Parameter Number
AO 32 Write Parameter Data
u
Metasys N2 Binary Input (BI) Summary
Table F.7 Metasys N2 Binary Input Summary (Bypass to Metasys N2)
Object ID Object Name Default Off (0) State On (1) State
BI 1 Run/Stop Monitor 0 Stopped Running
BI 2 Forward/Reverse Monitor 0 Forward Reverse
BI 3 Drive Ready Monitor 0 Not Ready Ready
BI 4 Fault Monitor 0 Not Faulted Faulted
BI 5 Zero Speed 0 Not Zero Speed Zero Speed
BI 6 Speed Agree 0 Not Speed Agree Speed Agree
BI 7 Minor Fault 0 No Minor Fault Minor Fault
BI 8 Major Fault 0 No Major Fault Major Fault
BI 9 Drive Communication Error Monitor 0 No Error Error
F.6 Metasys N2 Point Database