Object ID Object Name
Modbus
Address
Active Text Inactive Text PV Access
B011 BYP DO-10 COMMAND 8403H:bit 9 ON OFF C
u
Binary Value Objects
Table C.9 Binary Value Objects
Object ID Object Name
Modbus
Address
Active Text Inactive Text PV Access
BV1 Not Used BV1
BV2 Not Used BV2
BV3 Ext Fault Cmd 8480H:bit 2 FAULT OFF C
BV4 Fault Reset Cmd 8480H:bit 3 RESET OFF C
BV5 Not Used BV5
BV6 Not Used BV6
BV7 MF Input 3 Cmd 8480H:bit 6 ON OFF C
BV8 MF Input 4 Cmd 8480H:bit 7 ON OFF C
BV9 MF Input 5 Cmd 8480H:bit 8 ON OFF C
BV10 MF Input 6 Cmd 8480H:bit 9 ON OFF C
BV11 MF Input 7 Cmd 8480H:bit 10 ON OFF C
BV12 Set Fault Contact Cmd 0009H:bit 6 ENABLE OFF C
BV13 RUN-STOP 0020H:bit 0 RUN OFF R
BV14 REV-FWD 0020H:bit 1 REV FWD R
BV15 READY 0020H:bit 2 READY OFF R
BV16 FAULT 0020H:bit 3 FAULTED OFF R
BV17 Data Set Error 0020H:bit 4 ERROR OFF R
BV18 Overcurrent – Gnd Flt 0021H:bit 0 OC-GF OFF R
BV19 Main Ckt OverVoltage 0021H:bit 1 OV OFF R
BV20 Drive OverLoad 0021H:bit 2 OL2 OFF R
BV21 Drive OverHeat 0021H:bit 3 OH1-OH2 OFF R
BV22 Fuse Blown 0021H:bit 5 PUF OFF R
BV23 PI Feedback Loss 0021H:bit 6 FBL OFF R
BV24 External Fault 0021H:bit 7 EF0-EF OFF R
BV25 Hardware Error 0021H:bit 8 CPF OFF R
BV26 Mtr Ovrld-OvrTorque 0021H:bit 9 OL1-OL3 OFF R
BV27 OverSpeed 0021H:bit 10 OS-DEV OFF R
BV28 Main Ckt UnderVoltage 0021H:bit 11 UV OFF R
BV29 MCU Cntl Pwr Sy Err 0021H:bit 12 UV1-2-3 OFF R
BV30 Output Phase Loss 0021H:bit 13 LF OFF R
BV31 Communication Error 0021H:bit 14 CE OFF R
BV32 Operator Disconnect 0021H:bit 15 OPR OFF R
BV33 Operating 002CH:bit 0 OPERATING OFF R
BV34 Zero Speed 002CH:bit 1 ON OFF R
BV35 Frequency Agree 002CH:bit 2 ON OFF R
BV36 Desired Freq Agree 002CH:bit 3 ON OFF R
BV37 Frequency Detect 1 002CH:bit 4 ON OFF R
BV38 Frequency Detect 2 002CH:bit 5 ON OFF R
BV39 Drv Startup Complete 002CH:bit 6 ON OFF R
BV40 Low Voltage Detect 002CH:bit 7 ON OFF R
BV41 Base Block 002CH:bit 8 ON OFF R
BV42 Frequency Ref Mode 8785H:bit 8 COM LOCAL R
BV43 Run Command Mode 8485H:bit 9 COM LOCAL R
C.6 BACnet Objects Supported