Setting 33: DRIVE/BYPASS Select
When this is selected, the DRIVE/BYPASS select function command will come from a digital input while the DRV/BYP key
on the HOA operator will be ignored.
Input OFF: Drive Mode is selected.
Input ON: Bypass Mode is selected.
Setting 34: Fault Reset
Resets any faults that are present.
Setting 35: External Fault (EF0)
Issues external fault EF0 to the drive from the bypass. Use parameter Z1-30 to modify the fault delay time.
Setting 36: External Fault (EFB)
Triggers external EFB on the bypass.
Setting 37: Run Reverse (AUTO Mode)
Starts and stops the bypass in reverse when Z1-08 is set to 1.
Setting 38: Fire Stat
Stops the drive from running and displays "Fire Stat" on the keypad regardless of Z1-08 setting.
Note: Available in bypass controller software versions VST800400 and later.
Setting 39: Freeze Stat
Stops the drive from running and displays "Freeze Stat" on the keypad regardless of Z1-08 setting.
Note: Available in bypass controller software versions VST800400 and later.
Setting 40: Smoke Alarm
Stops the drive from running and displays "Smoke Alarm" on the keypad regardless of Z1-08 setting.
Note: Available in bypass controller software versions VST800400 and later.
Setting 41: Over Pressure
Stops the drive from running and displays "Over Pressure" on the keypad regardless of Z1-08 setting.
Note: Available in bypass controller software versions VST800400 and later.
Setting 42: Low Suction
Stops the drive from running and displays "Low Suction" on the keypad regardless of Z1-08 setting.
Note: Available in bypass controller software versions VST800400 and later.
Setting 43: Vibration Switch
Stops the drive from running and displays "Vibration Switch" on the keypad regardless of Z1-08 setting.
Note: Available in bypass controller software versions VST800400 and later.
n
Z2-09 to Z2-16: Digital Input 1 to 8 Invert Select
No.
Name Setting Range Default
Z2-09 Digital Input 1 Invert Select 0, 1 0
Z2-10 Digital Input 2 Invert Select 0, 1 0
Z2-11 Digital Input 3 Invert Select 0, 1 0
Z2-12 Digital Input 4 Invert Select 0, 1 0
Z2-13 Digital Input 5 Invert Select 0, 1 0
Z2-14 Digital Input 6 Invert Select 0, 1 0
Z2-15 Digital Input 7 Invert Select 0, 1 0
Z2-16 Digital Input 8 Invert Select 0, 1 0
5.15 Z: Bypass Parameters
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
211
5
Programming