Step Display/Result
5.
Save the setting by pressing .
Entry Accepted
6. The display automatically returns to the display shown in Step 3.
DRV-OFF
T1-01= 3 *3*
V/f Engy Sav Tun
Tuning Mode Sel
DATAESC
n
Enter Data from the Motor Nameplate
After selecting the type of Auto-Tuning, enter the data required from the motor nameplate.
Note: These instructions continue from Step 6 in “Selecting the Type of Auto-Tuning”.
Step Display/Result
1.
Press to access the motor output power parameter T1-02.
DRV-OFF
T1-02= 0.75kW
(0.00 - 650.00)
“0.75kW”
Mtr Rated Power
DATAESC
2.
Press to view the default setting.
DRV-OFF
T1-02= 000.75kW
(0.00 - 650.00)
“0.75kW”
Mtr Rated Power
3.
Press
F1
left
,
F2
right
, , , and to enter the motor power nameplate data in
kW.
DRV-OFF
T1-02= 000.40kW
(0.00 - 650.00)
“0.75kW”
Mtr Rated Power
4.
Press to save the setting.
Entry Accepted
5. The display automatically returns to the display in Step 1.
DRV-OFF
T1-02= 0.40kW
(0.00 - 650.00)
“0.75kW”
Mtr Rated Power
DATAESC
6.
Repeat Steps 1 through 5 to set the following parameters:
T1-03, Motor Rated Voltage
T1-04, Motor Rated Current
T1-05, Motor Base Frequency
T1-06, Number of Motor Poles
T1-07, Motor Base Frequency
DRV-OFF
T1-03= 200.0VAC
(0.00 - 255.00)
“200.0VAC”
Rated Voltage
DATAESC
DRV-OFF
T1-10= X.XXHz
(0.00 - 20.00)
“X.XX Hz”
Mtr Rated Slip
DATAESC
Note: 1. For details on each setting, Refer to T1: Parameter Settings during Induction Motor Auto-Tuning on page 114.
2. To execute Stationary Auto-Tuning for line-to-line resistance only, set parameters T1-02 and T1-04.
4.7 Auto-Tuning
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
113
4
Start-Up Programming
& Operation