<1> Values are given in Hz, but actual values are dependent upon unit settings using drive parameters o1-03, o1-09, o1-10, and o1-11.
n
Z1-15: Interlock Wait Time
When an input is programmed for Interlock and the time set to this parameter is reached before the Interlock input goes active,
a fault will be declared. The default setting of 0.0 will never time out.
No. Name Setting Range Default
Z1-15 Interlock Wait Time 0.0 to 300.0 s 0.0 s
Run Delay with Preset Speed Examples
VFD RUN COMMAND
VFD OUTPUT FREQUENCY
DAMPER ACTUATOR OUTPUT
BAS INTERLOCK INPUT
t1 t2 t3
VFD FREQUENCY REFERENCE
Parameter Settings:
Z1-12 Run Delay Time = 0.0 sec
Z1-13 Pre Int Run Sel = 0 (Disabled)
Z1-14 Run Delay Fref = 60.0 Hz
Z1-15 Interlck Wait Tm = 0.0 sec (Never Time Out)
Figure 5.56 Run Delay with Preset Speed Example: Default Setting
5.15 Z: Bypass Parameters
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
199
5
Programming