HOA Keypad Display Fault Name
A general-purpose motor is driven below the rated
speed with a high load
Reduce the load.
Increase the speed.
If the motor is supposed to operate at low speeds, either increase the motor capacity or use a motor
specifically designed to operate in the desired speed range.
The wrong motor rated current is set to E2-01
Check the motor-rated current.
Enter the motor rated current to parameter E2-01 as indicated on the motor nameplate.
The maximum output frequency is set incorrectly Check the E1-03 setting.
Multiple motors are running off the same bypass Set L1-01 to 0 to disable the motor protection function and then install a thermal relay to each motor.
The electrical thermal protection characteristics
and motor overload characteristics do not match.
Check the motor characteristics.
Correct the type of motor protection that has been selected (L1-01).
Install an external thermal relay.
The electrical thermal relay is operating at the
wrong level.
Check the current rating listed on the motor nameplate.
Check the value set for the motor rated current (E2-01)
HOA Keypad Display Fault Name
FB06
External Motor 1 Overload
Note: A fault reset is not required. An EF0 is sent to the drive and bypass Contactor K3 is
opened.
External overload input is active for motor 1
Cause Possible Solution
Load is too heavy Reduce the load.
Cycle times are too short during acceleration and
deceleration
Increase the acceleration and deceleration times (C1-01 and C1-02).
A general-purpose motor is driven below the rated
speed with a high load
Reduce the load.
Increase the speed.
If the motor is supposed to operate at low speeds, either increase the motor capacity or use a motor
specifically designed to operate in the desired speed range.
HOA Keypad Display Fault Name
FB07
External Motor 2 Overload
Note: A fault reset is not required. An EF0 is sent to the drive and bypass contactor K3 is
opened.
External overload input is active for motor 2
Cause Possible Solution
Load is too heavy Reduce the load.
Cycle times are too short during acceleration and
deceleration
Increase the acceleration and deceleration times (C1-01 and C1-02).
A general-purpose motor is driven below the rated
speed with a high load
Reduce the load.
Increase the speed.
If the motor is supposed to operate at low speeds, either increase the motor capacity or use a motor
specifically designed to operate in the desired speed range.
HOA Keypad Display Fault Name
FB08
Phase Loss Brownout
Note: A fault reset is required. An EF0 is sent to the drive and drive output contactor K2 and
Bypass contactor K3 are opened.
The contactor coil voltage was continuously detected below the configured brownout voltage level
for the configured brownout time.
Cause Possible Solution
Input power is too low. Verify input power is sufficient to power the bypass.
Settings for brownout are incorrect. Verify Z1-27 (Brownout Voltage Level) and Z1-28 (Brownout Time) are set properly.