EasyManua.ls Logo

YASKAWA Z1000 - Page 236

YASKAWA Z1000
466 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
HOA Keypad Display Fault Name
External cooling fan has malfunctioned
Cycle power to the drive.
Check for fan operation.
Verify the cumulative operation time of the fan with monitor U4-03, and verify the cumulative
operation time of the fan maintenance timer with U4-04.
If the cooling fan has exceeded its expected performance life or is damaged in any other way, follow
the replacement instructions in the Periodic Inspection & Maintenance chapter.
HOA Keypad Display Fault Name
FbH
Excessive PI Feedback
PI feedback input is greater than the level set to b5-36 for longer than the time set to b5-37. Set b5-12
to 2 or 5 to enable fault detection.
Cause Possible Solution
Parameters are set inappropriately Check b5-36 and b5-37 settings.
Incorrect PI feedback wiring Correct the wiring.
There is a problem with the feedback sensor
Check the sensor on the control side.
Replace the sensor if damaged.
HOA Keypad Display Fault Name
FbL
PI Feedback Loss
This fault occurs when PI feedback loss detection is programmed to trigger a fault (b5-12 = 2) and
the PI feedback level is below the detection level set to b5-13 for longer than the time set to b5-14.
Cause Possible Solution
Parameters are set inappropriately Check b5-13 and b5-14 settings.
Incorrect PI feedback wiring Correct the wiring.
There is a problem with the feedback sensor
Check the sensor on the control side.
Replace the sensor if damaged.
HOA Keypad Display Fault Name
GF
Ground Fault
A current short to ground exceeded 50% of rated current on the output side of the drive.
Setting L8-09 to 1 enables ground fault detection in models Z1B1D074 to D273 and B052 to B302.
Cause Possible Solution
Motor insulation is damaged
Check the insulation resistance of the motor.
Replace the motor.
A damaged motor cable is creating a short circuit
Check the motor cable.
Remove the short circuit and reapply power to the drive
Check the resistance between the cable and the ground terminal .
Replace the cable.
Excessive leakage current at the drive output
Reduce the carrier frequency.
Reduce the amount of stray capacitance.
The drive started to run during a current offset fault
or while coasting to a stop
Set b3-01 to 1 to enable Speed Search at Start.
Hardware problem
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
HOA Keypad Display Fault Name
LF
Output Phase Loss
Phase loss on the output side of the drive.
Setting L8-07 to 1 or 2 enables Phase Loss Detection.
Cause Possible Solution
The output cable is disconnected
Check for wiring errors and properly connect the output cable.
Correct the wiring.
The motor winding is damaged
Check the resistance between motor lines.
Replace the motor if the winding is damaged.
The output terminal is loose
Apply the tightening torque specified in this manual to fasten the terminals. Refer to Wire Gauge
and Tightening Torque Specifications on page 62 for details.
6.4 Fault Detection
236
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual

Table of Contents

Other manuals for YASKAWA Z1000

Related product manuals