Figure 7.10 Plug the Fan Connector: 2A0011 to 2A0059, 4A0005 to 4A0040, and 4A0052ooB
5.
Push the fan connector and protective tube into the fan finger guard.
Figure 7.11 Placement of Fan Connector and Protective Tube: 2A0011 to 2A0059, 4A0005 to 4A0040, and 4A0052ooB
6.
While pressing in on the hooks on the left and right sides of the fan finger guard, guide the fan finger guard until it
clicks into place.
Figure 7.12 Reattach the Cooling Fan and Fan Finger Guard: 2A0011 to 2A0059, 4A0005 to 4A0040, and 4A0052ooB
7.5 Drive Cooling Fans
280
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual