Table B.5 480 V Default Settings by Model Selection
No. Name Unit Default Settings
Bypass Model Z1B1
B001
B002
B003
B004
B007 B011 B014 B021 B027
o2-04 Drive Model Selection Hex. 94 96 98 99 9A 9C
b3-04 V/f Gain during Speed Search % 100 100 100 100 100 100
b3-06 Output Current 1 during Speed Search 0.5 0.5 0.5 0.5 0.5 0.5
b3-08
Current Control Gain during Speed Search (Speed
Estimation Type)
0.50 0.50 0.50 0.50 0.50 0.50
b3-11
Speed Search Method Switching Level (Speed
Estimation Type)
5.0 5.0 5.0 5.0 5.0 5.0
C6-02 Carrier Frequency Selection 2 2 2 2 2 2
E2-01 Motor Rated Current A 4.80 7.60 11.00 14.00 21.0 27.0
E2-03 Motor No-Load Current A 1.5 2.3 2.6 4 5.6 7.6
L2-03
Momentary Power Loss Minimum Baseblock
Time
s 0.5 0.6 0.7 0.8 0.9 1.0
L2-05 Undervoltage Detection Level (Uv1) 380 380 380 380 380 380
L8-02 Overheat Alarm Level °C 75 75 75 95 95 95
L8-06 Input Phase Detection Level 14.0 15.0 17.0 24.0 27.0 25.0
L8-09 Output Ground Fault Detection Selection 0 0 0 0 0 0
L8-38 Carrier Frequency Reduction 2 2 2 2 2 2
No. Name Unit Default Settings
Bypass Model Z1B1 B034 B040 B52L B052 B065 B077 B096
o2-04 Drive Model Selection Hex. 9D 9E
9F
or
(B0)
<1>
9F
or
(B0)
<1>
A1
or
(B1)
<2>
A2
or
(B2)
<3>
A3
b3-04 V/f Gain during Speed Search % 100 100 100 100 100 100 80
b3-06 Output Current 1 during Speed Search 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-08
Current Control Gain during Speed
Search (Speed Estimation Type)
0.50 0.50 0.50 0.50 0.50 0.50 0.50
b3-11
Speed Search Method Switching Level
(Speed Estimation Type)
5.0 5.0 5.0 5.0 5.0 5.0 5.0
C6-02 Carrier Frequency Selection 2 2 2 2 2 2 2
E2-01 Motor Rated Current A 34.0 40.0 52.0 52.0 65.0 77.0 96.0
E2-03 Motor No-Load Current A 7.8 9.2 10.9 10.9 19.1 22 24
L2-03
Momentary Power Loss Minimum
Baseblock Time
s 1.0 1.0 1.1 1.1 1.1 1.2 1.2
L2-05 Undervoltage Detection Level (Uv1) 380 380 380 380 380 380 380
L8-02 Overheat Alarm Level °C 100 100 102 102 102 102 102
L8-06 Input Phase Detection Level 30.0 24.0 24.0 24.0 24.0 24.0 25.0
L8-09
Output Ground Fault Detection
Selection
0 0 1 1 1 1 1
L8-38 Carrier Frequency Reduction 2 2 2 2 2 2 2
<1> Set o2-04 to B0 for Z1000 chassis drives with Rev: B in the nameplate model field.
<2> Set o2-04 to B1 for Z1000 chassis drives with Rev: B in the nameplate model field.
<3> Set o2-04 to B2 for Z1000 chassis drives with Rev: B in the nameplate model field.
B.15 Defaults by Drive Model
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
357
B
Parameter List