Setting 4: Alarm and run at preset speed set in Z3-10
Display AL14 alarm on operator.
n
Z3-08, Z3-09: BACnet Device Object Identifier
These parameters set the Instance Identifier of the BACnet Device Object, where Z3-08 is the least significant word and Z3-09
is the most significant word.
No. Name Setting Range Default
Z3-08 BACnet Device Object Identifier 0 0 to FFFFH 1
Z3-09 BACnet Device Object Identifier 1 0 to 003FH 0
Example 1: Set Device Object Instance Identifier of “1234”.
1234 decimal is equal to 4D2H (hexadecimal).
Set Z3-08 to 4D2H and set Z3-09 to 0.
Example 2: Set Device Object Instance Identifier of “123456”.
123456 decimal is equal to 1E240H.
Set Z3-08 to D687H and set Z3-09 to 12H.
n
Z3-13: BACNet Command Register Retention
Refer to Z3-13: BACNet Command Register Retention description on page 217.
C.4 BACnet Setup Parameters
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual