EasyManua.ls Logo

YASKAWA Z1000 - Page 394

YASKAWA Z1000
466 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Register No. Contents
0029H
Fault Contents 2
bit 0 Reserved
bit 1 Ground Fault (GF)
bit 2 Input Phase Loss (PF)
bit 3 Output Phase Loss (LF)
bit 4, bit 5 Reserved
bit 6 Motor Overheat 2 (PTC input) (oH4)
bit 7 to F Reserved
002AH
Alarm Contents 1
bit 0, 1 Reserved
bit 2 Run Command Input Error (EF)
bit 3 Drive Baseblock (bb)
bit 4 Overtorque Detection 1 (oL3)
bit 5 Heatsink Overheat (oH)
bit 6 Overvoltage (ov)
bit 7 Undervoltage (Uv)
bit 8 Cooling Fan Error (FAn)
bit 9 MEMOBUS/Modbus Communication Error (CE)
bit A Option Communication Error (bUS)
bit B Undertorque Detection 1 (UL3)
bit C Motor Overheat (oH3)
bit D PI Feedback Loss (FbL, FbH)
bit E Reserved
bit F Serial Communication Transmission Error (CALL)
002BH
Input Terminal Status
bit 0 Terminal S1 Closed
bit 1 Terminal S2 Closed
bit 2 Terminal S3 Closed
bit 3 Terminal S4 Closed
bit 4 Terminal S5 Closed
bit 5 Terminal S6 Closed
bit 6 Terminal S7 Closed
bit 7 to F Reserved
002CH
Drive Status 2
bit 0 During Run
bit 1 Zero Speed
bit 2 Speed Agree
bit 3 User Speed Agree
bit 4 Frequency Detection 1
bit 5 Frequency Detection 2
bit 6 Drive Ready
bit 7 During Undervoltage
bit 8 During Baseblock
bit 9 Frequency Reference from Operator Keypad
bit A Run Command from Operator Keypad
bit B Over/Undertorque 1
bit C Frequency Reference Loss
bit D During Fault Restart
bit E Fault
bit F Communication Timeout
D.9 MEMOBUS/Modbus Data Table
394
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual

Table of Contents

Other manuals for YASKAWA Z1000

Related product manuals