<9. Advanced Engineering >
TI 34P02K35-02E
May 31, 2017-00
_MVTRK_ACT_SW (Output tracking SW) Default: OFF
_AUT_FLBK_SW (AUT fallback switch) Default: OFF
To enable I/O compensation, gap, deadband, output tracking or AUT fallback
function, modify the respective switch to ON.
_ANS_IN_SW (Answerback input action direction switch) Default:
Forward
_ANS_CHK_SW (Answerback check monitoring action switch) Default:
both sides
_ANS_TRK_SW (Answerback tracking action switch) Default: ON
_SIO_OUT_DIR_SW (Output signal conversion action direction switch)
Default: Forward
These engineering parameters are related to switch instrument POUs
(NPAS_SIO_**). Modify these parameter values as required.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA STARDOM FCN-RTU and is the answer not in the manual?

YOKOGAWA STARDOM FCN-RTU Specifications

General IconGeneral
ModelFCN-RTU
CategoryController
Input Voltage24 VDC
Humidity Range5 to 95% RH (non-condensing)
Enclosure RatingIP20
TypeRemote Terminal Unit
Communication ProtocolsModbus, Ethernet/IP, DNP3, IEC 60870-5-101/104
Communication InterfacesRS-232, RS-485, Ethernet
Input/OutputDigital and Analog I/O
Power Supply24 VDC
Operating Temperature-20 to 60 °C
Programming LanguagesST (Structured Text), LD (Ladder Diagram), FBD (Function Block Diagram)