NUMBER DATA VALUE HEADING TEXT
43 Oil Sump Pressure Oil Sump
44 Oil Differential Pressure Oil Diff Pressure
45 Oil Pump Command Frequency Oil Pump Cmd Freq
46 Oil Pump Pressure Setpoint Oil Pump Pres Setp
47 Proximity Differential Prox Diff
48 Thrust Bearing Limit Switch Thrust Limit Swtch
49 Stall Detector Board Output Voltage Stall Det Volt
50 HGBP Valve Opening HGBP Valve Open
51 HGBP Valve Closing HGBP Valve Close
VSD DATA
# Data Value Heading Text
52 ACC Delta P / P ACC Delta P/P
53 ACC Surge Detection ACC Surge
54 ACC Surge Frequency ACC Surge Freq
55 ACC Surge Map Count ACC Map Count
56 VSD Command Frequency VSD Cmd Freq
57 VSD Output Frequency VSD Output Freq
58 VSD Control Mode (Auto/Manual) VSD Mode
59 VSD DC Bus Voltage (Highest of the 6 for MVVSD) VSD DC Bus
60 VSD Output Voltage VSD Output Volt
61 VSD Phase A Current VSD Phase A Cur
62 VSD Phase B Current VSD Phase B Cur
63 VSD Phase C Current VSD Phase C Cur
64 VSD Trigger SCR On VSD SCR On
65 VSD Converter Heatsink Temperature VSD Conv Temp
66 VSD Phase A Heatsink Temperature VSD Phase A Temp
67 VSD Phase B Heatsink Temperature VSD Phase B Temp
68 VSD Phase C Heatsink Temperature VSD Phase C Temp
69 VSD Inverter Baseplate Temperature VSD Inv Temp
IEEE 519 DATA
# Data Value Heading Text
70 Filter Running Filter Run
71 Filter Precharge Contactor Filter Precharge
72 Filter Supply Contactor Filter Contactor
73 Filter DC Bus Filter DC Bus
74 Filter Baseplate Temperature Filter Base Temp
75 Filter L1 – L2 RMS Voltage Filter L1-L2 Volt
76 Filter L2 – L3 RMS Voltage Filter L2-L3 Volt
77 Filter L3 – L1 RMS Voltage Filter L3-L1 Volt
78 Filter L1 – N Peak Voltage Filter L1-N Volt
79 Filter L2 – N Peak Voltage Filter L2-N Volt
80 Filter L3 – N Peak Voltage Filter L3-N Volt
81 Filter L1 RMS Filter Current Filter L1 Filter Cur
82 Filter L2 RMS Filter Current Filter L2 Filter Cur
SI0271 - SOFTWARE ENHANCEMENTS (VER 25) EFFECTIVE AUGUST 2013 (CONT'D)
TABLE 33 - DATA LOGGING (CONT'D)