380
FORM 160.54-M1
ISSUE DATE: 10/25/2019
SECTION 36 - SOFTWARE ENHANCEMENTS
JCI COMPANY CONFIDENTIAL JOHNSON CONTROLS
NUMBER DATA VALUE HEADING TEXT
83 Filter L3 RMS Filter Current Filter L3 Filter Cur
84 Filter L1 RMS Supply Current Filter L1 Supply Cur
85 Filter L2 RMS Supply Current Filter L2 Supply Cur
86 Filter L3 RMS Supply Current Filter L3 Supply Cur
87 Filter Maximum Total Demand Distortion Filter Max Demand
SSS DATA
# Data Value Heading Text
52 SSS Phase A Current SSS Phase A Cur
53 SSS Phase B Current SSS Phase B Cur
54 SSS Phase C Current SSS Phase C Cur
55 SSS Phase A Voltage SSS Phase A Volt
56 SSS Phase B Voltage SSS Phase B Volt
57 SSS Phase C Voltage SSS Phase C Volt
LCSSS DATA
# Data Value Heading Text
52 LCSSS Phase A Current LCSSS Phase A Cur
53 LCSSS Phase B Current LCSSS Phase B Cur
54 LCSSS Phase C Current LCSSS Phase C Cur
55 LCSSS Phase A Voltage LCSSS Phase A Volt
56 LCSSS Phase B Voltage LCSSS Phase B Volt
57 LCSSS Phase C Voltage LCSSS Phase C Volt
58 LCSSS Phase A Temperature LCSSS Phase A Temp
59 LCSSS Phase B Temperature LCSSS Phase B Temp
60 LCSSS Phase C Temperature LCSSS Phase C Temp
Seal Lubrication Timer and Warning
When Standby Lube is enabled, seal lubrication is per-
formed by running the Oil Pump for two minutes. Seal
lubrication is performed once every twenty-four hours
since the Oil Pump was last run for at least two min-
utes. It was found that the twenty-four hour time period
could drift by several hours. This was corrected. Also,
the “Warning – Seal Lubrication In Progress” was
changed to be a non-annunciating warning.
Remote Analog Hot Water Setpoint
The Hot Water Setpoint on the Heat Recovery screen
did not control the remote analog signal when in Re-
mote Source at View Access level. The setpoint worked
properly in Service mode. This has been corrected to
work properly in all access modes.
SI0271 - SOFTWARE ENHANCEMENTS (VER 25) EFFECTIVE AUGUST 2013 (CONT'D)
TABLE 33 - DATA LOGGING (CONT'D)