2)
Description
Terminal
1)
Connection
Safe torque off
×Safe torque off. Factory connection. Both cir-
cuits must be closed for the drive to start.
SGND34
OUT1
SGND
IN1
IN2
×IN135
×IN236
×OUT137
Auxiliary voltage input/output
Aux. voltage output +24 V DC, max. 250 mA
3)
+24V42
+24 V
DGND
DCOM
Aux. voltage output commonDGND43
Digital input common for allDCOM44
1)
Terminal size: 0.14 1.5 mm
2
(26 16 AWG) Tightening torque: 0.5 0.6 N·m (4.4 5.3 lbf·in)
2)
× = base unit, empty = RIIO-01 module
3)
The sum output current from 24 V terminals of base unit and RIIO-01 module must not exceed 250 mA.
4)
Drive output frequency:
Operation/ParameterDI4DI3
Set output frequency through AI100
28.26 Constant frequency 101
28.27 Constant frequency 210
28.28 Constant frequency 311
Default fieldbus connection diagram
The connection diagrams are applicable to the base unit with an optional fieldbus
adapter module.
2)
Description
Terminal
1)
Connection
Auxiliary voltage output and digital inputs
×Aux. voltage output +24 V DC, max. 250 mA+24V10
+24 V
DGND
DCOM
DI1
DI2
+24 V
DGND
DC
OM
DI1
DI2
×Aux. voltage output commonDGND11
×Digital input common for allDCOM12
×Stop (0) / Start (1)DI113
×Not configuredDI214
104 Electrical installation North America