65 kA when protected by fuses given in the fuse tables.Rated conditional
short-circuit current
I
cc
(IEC 61800-5-1)
US and Canada: The drive is suitable for use on a circuit capable of
delivering not more than 100 kA symmetrical amperes (rms) at 480 V
maximum when protected by fuses given in the fuse table.
Maximum prospect-
ive short-circuit cur-
rent rating (SCCR)
(UL 61800-5-1,
CSA C22.2 No. 274-13)
Refer to Compliance with the harmonic current limits in a public
network (IEC/EN 61000 3-2, IEC/EN 61000-3-12) (page 177).
Harmonic current
limits in public net-
work
(IEC/EN 61000-3-2,
IEC/EN 61000-3-12)
Refer to Input chokes (page 205) for general guidelines on the use of
the choke.
Input choke
Use an input choke, if the short-circuit capacity of the network at
the drive terminals is more than specified in this table:
R3, R4R0, R1, R2Input voltage
->1.5 kA1-phase 200 … 240 V
>7.5 kA>5.0 kA3-phase 200 … 240 V
>10 kA>5.0 kA3-phase 380 … 480 V
Suitable chokes are given in this manual. You can use one choke for
several drives if the short-circuit capacity at the drive terminals is
decreased to the value in the table.
47 … 63 Hz, maximum rate of change 2%/sFrequency (f1)
Max. ±3% of nominal phase to phase input voltageImbalance
0.98 (at nominal load)Fundamental power
factor (cos phi)
Motor connection data
Asynchronous AC induction motors, permanent magnet synchronous
motors or ABB synchronous reluctance motors (SynRM motors)
Motor type
0 … U1, 3-phase symmetricalVoltage (U2)
The motor output is short-circuit proof by IEC 61800-5-1 and UL
61800-5-1.
Short-circuit protec-
tion (IEC 61800-5-1,
UL 61800-5-1)
0 … 599 HzFrequency (f2)
0.01 HzFrequency resolution
Technical data 167