Connecting the power cables North America (wiring in
conduits)
Use insulated wires suitable for installation in electrical conduits. See the National
Electric Code and local ordinances.
Connection diagram
PE
PE
L1 L2 L3 R-
R+
UDC+
UDC-
U1 W1
PE
T1/
U
T2/
V
T3/
W
V1
1
2
3
4
5
6
7
PE
L1 L2 L3
(L) (N)
M
3
Drive1
Drive enclosure2
Supply disconnecting device and fuses3
Input power wiring4
Protective earth (ground) conductor(s)5
Motor wiring
Note: ABB recommends to use a symmetrical shielded cable (VFD cable) as the motor
cable.
6
Brake resistor (optional)7
Electrical installation North America 99