EasyManua.ls Logo

ABB ACH480 - Definitions

ABB ACH480
264 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FrameOutput ratingsInput currentUL (NEC)
type
ACH480-
04-…
Light-duty useMax. cur-
rent
With chokeNo choke
P
Ld
I
Ld
I
max
I
1Ld
I
1Ld
hpAAAA
R27.511.016.911.013.9011A-4
R310.014.022.714.018.8014A-4
R315.021.030.621.026.6021A-4
R420.027.045.027.033.7027A-4
R425.034.057.634.041.3034A-4
R430.042.081.042.046.9042A-4
Definitions
The ratings are valid at a maximum surrounding air temperature of 50 °C (122 °F),
with the default drive switching frequency of 4 kHz (parameter 97.01), and with
an installation altitude below 1000 m (3281 ft).
U
n
Nominal input voltage of the drive. For input voltage range U1, refer
to Electrical power network specification (page 166).
I
1n
Nominal input current with typical motor power
P
n
. Continuous rms
input current, for dimensioning cables and fuses.
I
1Ld
Light-duty input current (rms) with typical motor power
P
Ld
, for
dimensioning cables and fuses.
I
max
Maximum output current. Available for 2 seconds every 10 minutes
when the output frequency is less than 9 Hz. Maximum current setting
(parameter
30.17
) can also limit the value.
I
n
Nominal output current. Maximum continuous rms output current
(no overload).
P
n
Typical motor power in nominal use (no overloading). The kilowatt
ratings are applicable to most IEC 4-pole motors.
I
Ld
Continuous rms output current. Allows 10% overload for 1 minute
every 10 minutes.
P
Ld
Typical motor power in light-duty use (10% overload). The kilowatt
ratings are applicable to most IEC 4-pole motors. The horsepower
ratings are applicable to most NEMA 4-pole motors.
134 Technical data

Table of Contents

Other manuals for ABB ACH480