FrameOutput ratingsInput currentUL (NEC)
type
ACH480-
04-…
Light-duty useMax. cur-
rent
With chokeNo choke
P
Ld
I
Ld
I
max
I
1Ld
I
1Ld
hpAAAA
R27.511.016.911.013.9011A-4
R310.014.022.714.018.8014A-4
R315.021.030.621.026.6021A-4
R420.027.045.027.033.7027A-4
R425.034.057.634.041.3034A-4
R430.042.081.042.046.9042A-4
■
Definitions
The ratings are valid at a maximum surrounding air temperature of 50 °C (122 °F),
with the default drive switching frequency of 4 kHz (parameter 97.01), and with
an installation altitude below 1000 m (3281 ft).
U
n
Nominal input voltage of the drive. For input voltage range U1, refer
to Electrical power network specification (page 166).
I
1n
Nominal input current with typical motor power
P
n
. Continuous rms
input current, for dimensioning cables and fuses.
I
1Ld
Light-duty input current (rms) with typical motor power
P
Ld
, for
dimensioning cables and fuses.
I
max
Maximum output current. Available for 2 seconds every 10 minutes
when the output frequency is less than 9 Hz. Maximum current setting
(parameter
30.17
) can also limit the value.
I
n
Nominal output current. Maximum continuous rms output current
(no overload).
P
n
Typical motor power in nominal use (no overloading). The kilowatt
ratings are applicable to most IEC 4-pole motors.
I
Ld
Continuous rms output current. Allows 10% overload for 1 minute
every 10 minutes.
P
Ld
Typical motor power in light-duty use (10% overload). The kilowatt
ratings are applicable to most IEC 4-pole motors. The horsepower
ratings are applicable to most NEMA 4-pole motors.
134 Technical data