Disconnecting the EMC filter or ground-to-phase varistor
Before you continue, refer to Compatibility of EMC filter and ground-to-phase
varistor with the grounding system (page 66).
To disconnect the EMC filter, remove the metal EMC screw.
To disconnect the ground-to-phase varistor, remove the metal VAR screw.
EMC/VAR screw location
Frames R0…R2
Frame R4Frame R3
68 Electrical installation IEC