Connection procedure
WARNING!
Obey the safety instructions of the drive. If you ignore them, injury or death,
or damage to the equipment can occur. If you are not a qualified electrical
professional, do not do installation, commissioning or maintenance work.
Refer to Terminal data for the power cables (page 163) for the tightening torques.
1. Do the steps in section Electrical safety precautions (page 18) before you start
the work.
2. Remove the screw on the drive front cover and lift the front cover up.
3. Attach the residual voltage warning sticker in the local language to the drive.
4. Strip the motor cable.
5. Ground the motor cable shield under the grounding clamp for 360-degree
grounding.
6. Twist the motor cable shield into a bundle, mark it with yellow-green insulation
tape, install a cable lug, and connect it to the grounding terminal.
72 Electrical installation IEC