EasyManua.ls Logo

ABB ACH480 - Connecting a PC; Installing options

ABB ACH480
264 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
To connect an external auxiliary power supply to the drive:
1. Install a BAPO-01 power extension module to the drive. See Installing
options (page 86).
2. Connect an external power supply to the +24V and DGND terminals of the base
unit.
For more information on the BAPO-01 module, see BAPO-01 auxiliary power
extension module (page 247).
RC
RA
RB
+24V DGND DCOM SGND S+
DI1
DI2
S1
S2
Connecting a PC
You can connect a PC to the drive. To communicate with the drive, the PC must
have suitable software (for example, Drive composer) installed.
If you have an assistant control panel (ACH-AP-H or ACH-AP-W), use a USB data
cable (Type A - Type Mini-B, maximum length 3 m [9.8 ft]) to connect to the PC.
Connect the cable as follows:
1. Open the USB connector cover on the control panel.
2. Connect the USB cable Mini-B plug to the control panel USB connector.
3. Connect the USB cable A plug to the USB port of the PC. The panel shows text
“USB connected”.
Note: You cannot use the control panel keys when the drive is connected to a PC.
If you have a RDUM-01 blank panel or CDPI-02 panel bus adapter installed, use a
BCBL-01 USB-RJ45 converter to connect to the PC.
It is also possible to use a CCA-01 configuration adapter when the drive is not
connected to the power supply network or to an external 24 V supply. The CCA-01
does not operate if the drive is powered.
Installing options
The drive has two option module slots:
Front option: Communication module slot under the front cover.
86 Electrical installation IEC