4)
Drive output frequency:
Operation/ParameterDI4DI3
Set output frequency through AI100
28.26 Constant frequency 101
28.27 Constant frequency 210
28.28 Constant frequency 311
Default fieldbus connection diagram
The connection diagrams are applicable to the base unit with an optional fieldbus
adapter module.
2)
Description
Terminal
1)
Connection
Auxiliary voltage output and digital inputs
×Aux. voltage output +24 V DC, max. 250 mA+24V10
+24 V
DGND
DCOM
DI1
DI2
+24 V
DGND
DC
OM
DI1
DI2
×Aux. voltage output commonDGND11
×Digital input common for allDCOM12
×Stop (0) / Start (1)DI113
×Not configuredDI214
Relay outputs
×Aux. voltage output +24 V DC, max. 250 mA+24V10
RO1C
RO1A
RO1B
+24 V
DGND
DCOM
×Aux. voltage output commonDGND11
×Digital input common for allDCOM12
×Damper control
250 V AC / 30 V DC, 2 A
CommonRO1C19
×Norm.
closed
RO1A20
×Norm. openRO1B21
Safe torque off
×Safe torque off. Factory connection. Both cir-
cuits must be closed for the drive to start.
SGND34
OUT1
SGND
IN1
IN2
×IN135
×IN236
×OUT137