ABB ACH480 - Terminal data for the control cables; Electrical power network specification

ABB ACH480
264 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PEL1, L2, L3, T1/U, T2/V, T3/W, R-, R+/
UDC+
UL (NEC)
type
ACH480-
04-…
Tightening
torque
MaximumMinimumTightening
torque
MaximumMinimum
lbf·inAWGAWGlbf·inAWGAWG
10.6101211…13618021A-4
25.74822…32218027A-4
25.74822…32218034A-4
25.74822…32218042A-4
Note:
The minimum specified wire size does not necessarily have sufficient current
carrying capacity at maximum load.
The terminals do not accept a conductor that is one size larger than the
maximum specified wire size.
The maximum number of conductors per terminal is 1.
Terminal data for the control cables
This table shows the control cable terminal data of the standard drive variant, that
is, the base unit with RIIO-01 I/O & EIA-485 module.
TorqueWire size
lbf·inN·mAWGmm
2
4.4…5.30.5…0.626…160.14…1.5
Electrical power network specification
Input voltage range:
ACH480-04-xxxx-1 drives: 1-phase 200 240 V AC -15% +10%.
Voltage (U1)
ACH480-04-xxxx-2 drives: 3-phase 200 240 V AC -15% +10%.
ACH480-04-xxxx-4 drives: 3-phase 380 480 V AC -15% +10%.
Public low voltage networks. Symmetrically grounded TN-S system,
IT (ungrounded), corner-grounded delta. Consult ABB before con-
necting to other systems (for example, TT, or midpoint grounded
delta).
Network type
166 Technical data