Connect the cable to the EIA-485 terminal on the RIIO-01 I/O module. Obey these
wiring instructions:
Attach the cable shields together at each drive, but do not connect them to
the drive.
Connect the cable shields only to the grounding terminal in the automation
controller.
Connect the signal ground (DGND) conductor to the signal ground reference
terminal in the automation controller. If the automation controller does not
have a signal ground reference terminal, connect the signal ground conductor
to the cable shield through a 100 ohm resistor, preferably near the automation
controller.
Connection examples are shown below.
With signal ground reference terminal
G R - +
1
DGND
2
DGND
2
DGND
2
3
3
3
ON
1
ON
1
ON
1
B+
A-
B+
A-
B+
A-
Without signal ground reference terminal
G - +
B+
A-
DGND
1
2
B+
A-
DGND
2
B+
A-
DGND
2
100 ohm
3 3 3
ON
1
ON
1
ON
1
Automation controller1
Drive2
Termination switch. The devices at the ends of the fieldbus must have termination
on. All other devices must have termination off.