FusesUL (NEC)
type
ACH480-
04-…
Max. fuse rat-
ing for group
installation
1)
Type
Bussmann/
Edison type
Voltage rating
Nominal cur-
rent
AVA
35UL class TJJN/TJN353003511A6-1
3-phase
U
n
= 230 V
25UL class TJJS/TJS6600602A3-2
25UL class TJJS/TJS106001003A5-2
25UL class TJJS/TJS106001004A6-2
25UL class TJJS/TJS156001506A6-2
25UL class TJJS/TJS156001507A5-2
30UL class TJJS/TJS206002011A6-2
40UL class TJJS/TJS3060030017A-2
40UL class TJJS/TJS4060040024A-2
100UL class TJJS/TJS5060050031A-2
100UL class TJJS/TJS7060070046A-2
3-phase
U
n
= 480 V
25UL class TJJS/TJS6600602A1-4
25UL class TJJS/TJS6600603A0-4
25UL class TJJS/TJS6600603A5-4
25UL class TJJS/TJS106001004A8-4
25UL class TJJS/TJS106001006A0-4
25UL class TJJS/TJS156001507A6-4
30UL class TJJS/TJS2060020011A-4
40UL class TJJS/TJS2560025014A-4
40UL class TJJS/TJS3560035021A-4
100UL class TJJS/TJS4560045027A-4
100UL class TJJS/TJS6060060034A-4
100UL class TJJS/TJS6060060042A-4
1)
Branch circuit short-circuit protection for group installation by fuses: Suitable for motor group
installation on a circuit that is capable of delivering no more than 65000 rms symmetrical amperes,
480 V maximum, when protected by class T fuses.
The same fuse size is specified for several consecutive drive types. This is possible since the physical
structure of the drive types is identical.
Technical data 145