Note: IEC/EN 61800-5-1 requires two separate PE (ground) conductors for a fixed
connection, if the cross-sectional area of the PE conductor is less than 10 mm
2
Cu.
FrameConductor size, Cu (AWG)
Cable size, Cu (mm
2
)
1)
IEC type
ACH480-
04-…
1-phase
U
n
= 230 V
R0143×1.5 + 1.502A4-1
R0143×1.5 + 1.503A7-1
R1143×1.5 + 1.504A8-1
R1143×1.5 + 1.506A9-1
R1143×1.5 + 1.507A8-1
R2143×2.5 + 2.509A8-1
R2143×2.5 + 2.512A2-1
3-phase
U
n
= 230 V
R1143×1.5 + 1.502A4-2
R1143×1.5 + 1.503A7-2
R1143×1.5 + 1.504A8-2
R1143×1.5 + 1.506A9-2
R1143×1.5 + 1.507A8-2
R1143×2.5 + 2.509A8-2
R2143×2.5 + 2.512A2-2
R3103×6 + 617A5-2
R3103×6 + 625A0-2
R483×10 + 10032A-2
R443×25 + 16048A-2
3-phase
U
n
= 400 V
R1143×1.5 + 1.502A7-4
R1143×1.5 + 1.503A4-4
R1143×1.5 + 1.504A1-4
R1143×1.5 + 1.505A7-4
R1143×1.5 + 1.507A3-4
R1143×2.5 + 2.509A5-4
R2143×2.5 + 2.512A7-4
Technical data 161