Parameters 125
35.53 Break point Defines the motor load curve together with parameters 35.51
Motor load curve and 35.52 Zero speed load. Defines the
break point frequency of the load curve ie. the point at which
the motor load curve begins to decrease from the value of
parameter 35.51 Motor load curve towards the value of
parameter 35.52 Zero speed load.
See parameter 35.51 Motor load curve.
45.00 Hz
1.00…500.00 Hz Break point for the motor load curve. 10 = 1 Hz
35.54 Motor nominal
temperature rise
Defines the temperature rise of the motor above ambient
when the motor is loaded with nominal current. See the motor
manufacturer's recommendations.
The unit is selected by parameter 96.16 Unit selection.
80 °C or
176 °F
0…300 °C or
32…572 °F
Temperature rise. 1 = 1°
No. Name/Value Description Def/FbEq16
Motor nominal
temperature rise
Temperature
Time
Ambient temperature
ACQ80 FW.book Page 125 Thursday, February 14, 2019 11:33 AM