132 Parameters
Motor
potentiometer
Not applicable.
Freq in scaled 11.39 Freq in 1 scaled value (see page 83). 10
AI1 percent 12.101 AI1 percent value (see page 88)11
AI2 percent 12.102 AI2 percent value (see page 88)12
Control panel (ref
saved)
Panel reference (03.01 Panel reference, see page 70) saved
by the control system for the location where the control
returns is used as the reference.
13
Control panel (ref
copied)
Panel reference (03.01 Panel reference, see page 70) for the
previous control location is used as the reference when the
control location changes if the references for the two
locations are of the same type (eg
frequency/speed/torque/PID); otherwise, the actual signal is
used as the new reference.
14
FB A ref1 03.05 FB A reference 1 (see page 70). 15
FB A ref2 03.06 FB A reference 2 (see page 70). 16
EFB ref1 03.09 EFB reference 1 (see page 71). 19
EFB ref2 03.10 EFB reference 2 (see page 71). 20
Setpoint data
storage
40.92 Setpoint data storage (see page 139)24
Other Source selection (see Terms and abbreviations on page 64). -
40.24 Set 1 internal
setpoint 0
Internal process setpoint 1. See parameter 40.16 Set 1
setpoint 1 source.
0.00
-200000.00...
200000.00
Internal process setpoint 1. 1 = 1
40.26 Set 1 setpoint min Defines a minimum limit for the process PID controller
setpoint.
0.00
-200000.00...
200000.00
Minimum limit for process PID controller setpoint. 1 = 1
40.27 Set 1 setpoint max Defines a maximum limit for the process PID controller
setpoint.
200000.00
-200000.00...
200000.00
Maximum limit for process PID controller setpoint. 1 = 1
40.28 Set 1 setpoint
increase time
Defines the minimum time it takes for the setpoint to increase
from 0% to 100%.
0.0 s
0.0…1800.0 s Setpoint increase time. 1 = 1
No. Name/Value Description Def/FbEq16
Ext1 -> Ext2
t
Reference
Ext1 reference
Ext2 reference
Active reference
Inactive reference
Ext1 -> Ext2
Ext1 reference
Ext2 reference
Active reference
t
Inactive reference
Reference
ACQ80 FW.book Page 132 Thursday, February 14, 2019 11:33 AM