Actual signals and parameters
81
16 SYSTEM
CONTROLS
Run Enable, parameter lock etc.
1601 RUN ENABLE Selects a source for the external Run Enable signal. 0 = NOT SEL
0 = NOT SEL Allows the drive to start without an external Run Enable signal.
1 = DI1 External signal required through digital input DI1. 1 = Run Enable. If Run
Enable signal is switched off, the drive will not start or coasts to stop if it is
running.
2 = DI2 See selection DI1.
3 = DI3 See selection DI1.
4 = DI4 See selection DI1.
5 = DI5 See selection DI1.
-1 = DI1(INV) External signal required through inverted digital input DI1. 0 = Run Enable.
If Run Enable signal is switched on, the drive will not start or coasts to stop if
it is running.
-2 = DI2(INV) See selection DI1(INV)
-3 = DI3(INV) See selection DI1(INV)
-4 = DI4(INV) See selection DI1(INV)
-5 = DI5(INV) See selection DI1(INV)
1602 PARAMETER LOCK Selects the state of the parameter lock. The lock prevents parameter
changing from control panel.
1 = OPEN
0 = LOCKED Parameter values cannot be changed from the control panel. The lock can be
opened by entering the valid code to parameter 1603 PASS CODE.
The lock does not prevent parameter changes made by macros.
1 = OPEN The lock is open. Parameter values can be changed.
2 = NOT SAVED Parameter changes made by control panel are not stored into the permanent
memory. To store changed parameter values, set parameter 1607 PARAM
SAVE value to SAVE.
1603 PASS CODE Selects the pass code for the parameter lock (see parameter 1602
PARAMETER LOCK).
0
0…65535 Pass code. Setting 358 opens the lock. The value reverts back to 0
automatically.
1604 FAULT RESET SEL Selects the source for the fault reset signal. The signal resets the drive after
a fault trip if the cause of the fault no longer exists.
0 = KEYPAD
0 = KEYPAD Fault reset only from the control panel
1 = DI1 Reset through digital input DI1 (reset by a rising edge of DI1) or by control
panel
2 = DI2 See selection DI1.
3 = DI3 See selection DI1.
4 = DI4 See selection DI1.
5 = DI5 See selection DI1.
7 = START/STOP Reset along with the stop signal received through a digital input, or by control
panel.
-1 = DI1(INV) Reset through inverted digital input DI1 (reset by a falling edge of DI1) or by
control panel
-2 = DI2(INV) See selection DI1(INV).
Parameters in the Long Parameter mode
Index Name/Selection Description Def