Actual signals and parameters
70
Actual signals
The following table includes the descriptions of all actual signal.
Actual signals
No. Name/Value Description
01 OPERATING DATA
Basic signals for monitoring the drive (read-only).
For actual signal supervision, see parameter group 32 SUPERVISION.
For selection of an actual signal to be displayed on the control panel, see parameter
group 34 PANEL DISPLAY.
0101 SPEED & DIR Calculated motor speed in rpm. A negative value indicates reverse direction.
0102 SPEED Calculated motor speed in rpm.
0103 OUTPUT FREQ Calculated drive output frequency in Hz. (Shown by default on the panel Output mode
display.)
0104 CURRENT Measured motor current in A
0105 TORQUE Calculated motor torque in percent of the motor nominal torque
0106 POWER Measured motor power in kW
0107 DC BUS VOLTAGE Measured intermediate circuit voltage in VDC
0109 OUTPUT VOLTAGE Calculated motor voltage in VAC
0110 DRIVE TEMP Measured IGBT temperature in °C
0111 EXTERNAL REF 1 External reference REF1 in Hz
0112 EXTERNAL REF 2 External reference REF2 in percent. 100% equals the maximum motor speed.
0113 CTRL LOCATION Active control location. (0) LOCAL; (1) EXT1; (2) EXT2.
0114 RUN TIME (R) Elapsed drive running time counter (hours). The counter can be reset by pressing the UP
and DOWN buttons simultaneously when the control panel is in Parameter mode.
0115 KWH COUNTER (R) kWh counter. The counter can be reset by pressing UP and DOWN buttons
simultaneously when the control panel is in Parameter mode.
0120 AI1 Relative value of analog input AI1 in percent
0121 POT Potentiometer value in percent
0137 PROCESS VAR 1 Process variable 1 defined by parameter group 34 PANEL DISPLAY
0138 PROCESS VAR 2 Process variable 2 defined by parameter group 34 PANEL DISPLAY
0139 PROCESS VAR 3 Process variable 3 defined by parameter group 34 PANEL DISPLAY
0140 RUN TIME Elapsed time counter (thousands of hours). Runs when the drive is running. Counter
cannot be reset.
0141 MWH COUNTER MWh counter. Counter cannot be reset.
0142 REVOLUTION CNTR Motor revolution counter (millions of revolutions). The counter can be reset by pressing
the UP and DOWN buttons simultaneously when the control panel is in Parameter mode.
0143 DRIVE ON TIME HI Drive control board power-on time in days. Counter cannot be reset.
0144 DRIVE ON TIME LO Drive control board power-on time in 2 second ticks (30 ticks = 60 seconds). Counter
cannot be reset.
0160 DI 1-5 STATUS Status of digital inputs. Example: 10000 = DI1 is on, DI2...DI5 are off.
0161 PULSE INPUT FREQ Value of frequency input in Hz
0162 RO STATUS Status of relay output. 1 = RO is energised, 0 = RO is de-energized.