Start-up and control with I/O
41
Set constant speeds (drive output frequencies) 1, 2 and 3
(parameters 1202, 1203 and 1204).
Set the minimum value (%) corresponding to the minimum
signal for AI(1) (parameter 1301).
Set the maximum limit for the drive output frequency
(parameter 2008).
Select the motor stop function (parameter 2102).
DIRECTION OF THE MOTOR ROTATION
Check the direction of the motor rotation.
Turn the potentiometer fully counterclockwise.
If the drive is in remote control (REM shown on the left),
switch to local control by pressing .
Press to start the motor.
Turn the potentiometer slightly clockwise until the motor
rotates.
Check that the actual direction of the motor is the same as
indicated in the display (FWD means forward and REV
reverse).
Press to stop the motor.
To change the direction of the motor rotation:
Disconnect input power from the drive, and wait 5 minutes
for the intermediate circuit capacitors to discharge. Measure
the voltage between each input terminal (U1, V1 and W1)
and earth with a multimeter to ensure that the drive is
discharged.
Exchange the position of two motor cable phase conductors
at the drive output terminals or at the motor connection box.
Verify your work by applying input power and repeating the
check as described above.
LOC s
PAR FWD
1202
LOC s
PAR FWD
1203
LOC s
PAR FWD
1204
LOC s
PAR FWD
1301
LOC s
PAR FWD
2008
LOC s
PAR FWD
2102
LOC
REM
LOC s
PAR FWD
2102
forward
direction
reverse
direction