Actual signals and parameters
85
2106 DC CURR REF Defines the DC braking current. See parameter 2104 DC HOLD CTL. 30
0…100% Value in percent of the motor nominal current (parameter 9906 MOTOR NOM
CURR)
2107 DC BRAKE TIME Defines the DC braking time. 0
0.0…250.0 s Time
2108 START INHIBIT Enables the start inhibit function. Drive start is inhibited if
- fault is reset.
- Run Enable signal activates while the start command is active. See
parameter 1601 RUN ENABLE.
- control mode changes from local to remote.
- external control mode switches from EXT1 to EXT2 or from EXT2 to EXT1.
0 = OFF
0 = OFF Disabled
1 = ON Enabled
2109 EMER STOP SEL Selects the source for the external emergency stop command.
The drive cannot be restarted before the emergency stop command is reset.
Note: The installation must include emergency stop devices and any other
safety equipment that may be needed. Pressing STOP on the drive’s control
panel does NOT
- generate an emergency stop of the motor.
- separate the drive from dangerous potential.
0 = NOT SEL
0 = NOT SEL Emergency stop function is not selected.
1 = DI1 Digital input DI1. 1 = stop along the emergency stop ramp. See parameter
2208 EMER DEC TIME. 0 = emergency stop command reset.
2 = DI2 See selection DI1.
3 = DI3 See selection DI1.
4 = DI4 See selection DI1.
5 = DI5 See selection DI1.
-1 = DI1(INV) Inverted digital input DI. 0 = stop along the emergency stop ramp. See
parameter 2208 EMER DEC TIME. 1 = emergency stop command reset
-2 = DI2(INV) See selection DI1(INV).
-3 = DI3(INV) See selection DI1(INV).
-4 = DI4(INV) See selection DI1(INV).
-5 = DI5(INV) See selection DI1(INV).
2110 TORQ BOOST CURR Defines the maximum supplied current during torque boost. See parameter
2101 START FUNCTION.
100
15…300% Value in percent
Parameters in the Long Parameter mode
Index Name/Selection Description Def