Planning electrical installation
24
Thermal overload and short-circuit protection
The drive protects itself and the input and motor cables against thermal overload
when the cables are dimensioned according to the nominal current of the drive. No
additional thermal protection devices are needed.
WARNING! If the drive is connected to multiple motors, a separate thermal overload
switch or a circuit breaker must be used for protecting each cable and motor. These
devices may require a separate fuse to cut off the short-circuit current.
Protection against short-circuit inside the drive or in the supply cable
Arrange the protection according to the following guidelines.
1) Size the fuses according to instructions given in chapter Technical data. The fuses will protect the input
cable in short-circuit situations, restrict drive damage and prevent damage to adjoining equipment in
case of a short-circuit inside the drive.
2) Circuit breakers which have been tested by ABB with the ACS150 can be used. Fuses must be used
with other circuit breakers. Contact your local ABB representative for the approved breaker types and
supply network characteristics.
The protective characteristics of circuit breakers depend on the type, construction and settings of the
breakers. There are also limitations pertaining to the short-circuit capacity of the supply network.
WARNING! Due to the inherent operating principle and construction of circuit
breakers, independent of the manufacturer, hot ionized gases may escape from the
breaker enclosure in case of a short-circuit. To ensure safe use, special attention
must be paid to the installation and placement of the breakers. Follow the
manufacturer’s instructions.
Protection against short-circuit in the motor and motor cable
The drive protects the motor and motor cable in a short-circuit situation when the
motor cable is dimensioned according to the nominal current of the drive. No
additional protection devices are needed.
Circuit diagram Short-circuit
protection
Protect the drive and
input cable with fuses
or a circuit breaker.
See footnotes 1) and
2).
M
3~
Distribution
board
Input cable
M
3~
Drive
1)
2)
I >