EasyManua.ls Logo

ABB ACS150 - Parameters in the Short Parameter Mode; Start-Up Data; Select

ABB ACS150
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Actual signals and parameters
66
Parameters in the Short Parameter mode
The following table describes the parameters that are visible in the Short Parameter
mode. See section Parameter modes on page 53 for how to select the parameter
mode. All parameters are presented in detail in section Parameters in the Long
Parameter mode, starting on page 72.
Parameters in the Short Parameter mode
No. Name/Value Description Def
99 START-UP DATA
Application macro. Definition of motor set-up data.
9902 APPLIC MACRO Selects the application macro or activates FlashDrop parameter values. See
chapter Application macros.
1 = ABB
STANDARD
1 = ABB STANDARD Standard macro for constant speed applications
2 = 3-WIRE 3-wire macro for constant speed applications
3 = ALTERNATE Alternate macro for start forward and start reverse applications
4 = MOTOR POT Motor potentiometer macro for digital signal speed control applications
5 = HAND/AUTO Hand/Auto macro to be used when two control devices are connected to the
drive:
- Device 1 communicates through the interface defined by external control
location EXT1.
- Device 2 communicates through the interface defined by external control
location EXT2.
EXT1 or EXT2 is active at a time. Switching between EXT1/2 through digital
input.
31 = LOAD FD SET FlashDrop parameter values as defined by the FlashDrop file.
FlashDrop is an optional device for fast copying of parameters to unpowered
drives. FlashDrop allows easy customisation of the parameter list, e.g.
selected parameters can be hidden. For more information, see MFDT-01
FlashDrop User’s Manual [3AFE68591074 (English)].
9905 MOTOR NOM VOLT Defines the nominal motor voltage. Must be equal to the value on the motor
rating plate. The drive cannot supply the motor with a voltage greater than
the input power voltage.
WARNING! Never connect a motor to a drive which is connected to power
line with voltage level higher than the rated motor voltage.
200
(US: 230)
400
(US: 460)
100...300 V (200 V /
US: 230 V units)
230...690 V (400 V /
US: 460 V units)
Voltage.
Note: The stress on the motor insulations is always dependent on the drive
supply voltage. This also applies to the case where the motor voltage rating
is lower than the rating of the drive and the supply of the drive.
9906 MOTOR NOM CURR Defines the nominal motor current. Must be equal to the value on the motor
rating plate.
I
2N
0.2…2.0 · I
2N
Current
Output voltage
Output frequency
9907
9905

Table of Contents

Other manuals for ABB ACS150

Related product manuals