Installation checklist
37
Installation checklist
Checklist
Check the mechanical and electrical installation of the drive before start-up. Go 
through the checklist below together with another person. Read chapter Safety on 
the first pages of this manual before you work on the drive.
Check
MECHANICAL INSTALLATION
The ambient operating conditions are allowed. (See Mechanical installation: Requirements 
for the installation site on page 20, Technical data: Cooling air flow requirements on page 115 
and Ambient conditions on page 121.)
The drive is fixed properly on an even vertical non-flammable wall. (See Mechanical 
installation.)
The cooling air will flow freely. (See Mechanical installation: Free space around the drive on 
page 21.)
The motor and the driven equipment are ready for start. (See Planning electrical installation: 
Motor selection on page 23 and Technical data: Motor connection on page 119.)
ELECTRICAL INSTALLATION (See Planning electrical installation and Electrical installation.)
For ungrounded and corner grounded systems: The internal EMC filter is disconnected 
(screw EMC removed).
The capacitors are reformed if the drive has been stored over two years. 
The drive is grounded properly.
The input power voltage matches the drive nominal input voltage.
The input power connections at U1, V1 and W1 are OK and tightened with the correct torque. 
Appropriate input power fuses and disconnector are installed.
The motor connections at U2, V2 and W2 are OK and tightened with the correct torque.
The motor cable is routed away from other cables.
The external control (I/O) connections are OK.
The input power voltage cannot be applied to the output of the drive (with a bypass 
connection). 
Terminal cover and, for NEMA 1, hood and connection box, are in place.