Actual signals and parameters
82
-3 = DI3(INV) See selection DI1(INV).
-4 = DI4(INV) See selection DI1(INV).
-5 = DI5(INV) See selection DI1(INV).
1606 LOCAL LOCK Disables entering local control mode or selects the source for the local
control mode lock signal. When local lock is active, entering the local control
mode is disabled (LOC/REM key of the panel).
0 = NOT SEL
0 = NOT SEL Local control is allowed.
1 = DI1 Local control mode lock signal through digital input DI1. Rising edge of digital
input DI1: Local control disabled. Falling edge of digital input DI1: Local
control allowed.
2 = DI2 See selection DI1.
3 = DI3 See selection DI1.
4 = DI4 See selection DI1.
5 = DI5 See selection DI1.
7 = ON Local control is disabled.
-1 = DI1(INV) Local lock through inverted digital input DI1. Rising edge of inverted digital
input DI1: Local control allowed. Falling edge of inverted digital input DI1:
Local control disabled.
-2 = DI2(INV) See selection DI1(INV).
-3 = DI3(INV) See selection DI1(INV).
-4 = DI4(INV) See selection DI1(INV).
-5 = DI5(INV) See selection DI1(INV).
1607 PARAM SAVE Saves the valid parameter values into the permanent memory. 0 = DONE
0 = DONE Saving completed
1 = SAVE Saving in progress
1610 DISPLAY ALARMS Activates/deactivates alarms OVERCURRENT (code: A2001),
OVERVOLTAGE (code: A2002), UNDERVOLTAGE (code: A2003) and
DEVICE OVERTEMP (code: A2009). For more information, see chapter
Fault tracing.
NO
0 = NO Alarms are inactive.
1 = YES Alarms are active.
1611 PARAMETER VIEW Selects the parameter view
Note: This parameter is visible only when it is activated by the optional
FlashDrop device. FlashDrop allows easy customisation of the parameter list,
e.g. selected parameters can be hidden. For more information, see MFDT-01
FlashDrop User’s Manual [3AFE68591074 (English)].
FlashDrop parameter values are activated by setting parameter 9902
APPLIC MACRO to LOAD FD SET.
0 = DEFAULT
0 = DEFAULT Complete long and short parameter lists
1 = FLASHDROP FlashDrop parameter list. Does not include short parameter list. Parameters
which are hidden by the FlashDrop device are not visible.
18 FREQ INPUT
Frequency input signal processing. Digital input DI5 can be programmed as
a frequency input. Frequency input can be used as external reference signal
source. See parameter 1103/1106 REF1/2 SELECT.
1801 FREQ INPUT MIN Defines the minimum input value when DI5 is used as a frequency input. 0
Parameters in the Long Parameter mode