Actual signals and parameters
96
0 = DISABLE Inactive
1 = ENABLE Active
3105 AR OVERVOLTAGE Activates/deactivates the automatic reset for the intermediate link
overvoltage fault. Automatically resets the fault (DC OVERVOLT, code:
F0002) after the delay set by parameter 3103 DELAY TIME.
0 = DISABLE
0 = DISABLE Inactive
1 = ENABLE Active
3106 AR UNDERVOLTAGE Activates/deactivates the automatic reset for the intermediate link
undervoltage fault. Automatically resets the fault (DC UNDERVOLTAGE,
code: F0006) after the delay set by parameter 3103 DELAY TIME.
0 = DISABLE
0 = DISABLE Inactive
1 = ENABLE Active
3107 AR AI<MIN Activates/deactivates the automatic reset for fault AI1 LOSS, code: F0007
(analog input signal under the allowed minimum level). Automatically resets
the fault after the delay set by parameter 3103 DELAY TIME.
0 = DISABLE
0 = DISABLE Inactive
1 = ENABLE Active
WARNING! The drive may restart even after a long stop if the
analog input signal is restored. Ensure that the use of this feature
will not cause danger.
3108 AR EXTERNAL FLT Activates/deactivates the automatic reset for the EXTERNAL FAULT 1/2
(code: F0014/0015). Automatically resets the fault after the delay set by
parameter 3103 DELAY TIME.
0 = DISABLE
0 = DISABLE Inactive
1 = ENABLE Active
Parameters in the Long Parameter mode
Index Name/Selection Description Def