Actual signals and parameters
88
2205 ACCELER TIME 2 Defines the acceleration time 2 i.e. the time required for the speed to change 
from zero to the speed defined by parameter 2008 MAXIMUM FREQ.
See parameter 2202 ACCELER TIME 1.
Acceleration time 2 is used also as jogging acceleration time. See parameter 
1010 JOGGING SEL.
60
0.0…1800.0 s Time
2206 DECELER TIME 2 Defines the deceleration time 2 i.e. the time required for the speed to change 
from the value defined by parameter 2008 MAXIMUM FREQ to zero.
See parameter 2203 DECELER TIME 1.
Deceleration time 2 is used also as jogging deceleration time. See parameter 
1010 JOGGING SEL.
60
0.0…1800.0 s Time
2207 RAMP SHAPE 2 Selects the shape of the acceleration/deceleration ramp 2. The function is 
deactivated during emergency stop (2109 EMER STOP SEL).
Ramp shape 2 is used also as jogging ramp shape time. See parameter 1010 
JOGGING SEL.
0
0.0…1000.0 s See parameter 2204 RAMP SHAPE 1.
2208 EMER DEC TIME Defines the time within the drive is stopped if an emergency stop is activated. 
See parameter 2109 EMER STOP SEL.
1
0.0…1800.0 s Time
2209 RAMP INPUT 0 Defines the source for forcing the ramp input to zero. 0 = NOT SEL
0 = NOT SEL Not selected
1 = DI1 Digital input DI1.1 = ramp input is forced to zero. Ramp output will ramp to 
zero according to the used ramp time.
2 = DI2 See selection DI1.
3 = DI3 See selection DI1.
4 = DI4 See selection DI1.
5 = DI5 See selection DI1.
-1 = DI1(INV) Inverted digital input DI1.0 = ramp input is forced to zero. Ramp output will 
ramp to zero according to the used ramp time.
-2 = DI2(INV) See selection DI1(INV).
-3 = DI3(INV) See selection DI1(INV).
-4 = DI4(INV) See selection DI1(INV).
-5 = DI5(INV) See selection DI1(INV).
Parameters in the Long Parameter mode
Index Name/Selection Description Def