Application macros
59
ABB Standard macro
This is the default macro. It provides a general purpose I/O configuration with three
constant speeds. Parameter values are the default values given in chapter Actual
signals and parameters, starting from page 65.
If you use other than the default connections presented below, see section I/O
terminals on page 34.
Default I/O connections
1…10 kohm
I/O connection
4)
SCR Signal cable shield (screen)
AI Frequency reference: 0…20 mA
GND Analog input circuit common
+10V Reference voltage: +10 VDC, max. 10 mA
+24V Auxiliary voltage output: +24 VDC, max. 200 mA
GND Auxiliary voltage output common
DCOM Digital input common
DI1 Stop (0) / Start (1)
DI2 Forward (0) / Reverse (1)
DI3 Constant speed selection
1)
DI4 Constant speed selection
1)
DI5 Acceleration and deceleration selection
2)
Relay connection
5)
COM Relay output
No fault [Fault (-1)]
NC
NO
3)
Alternative connection
for AI1. If used, switch
IU selector to U
(0…10 V voltage
signal).
1)
See parameter group 12 CONSTANT SPEEDS:
2)
0 = ramp times according to parameters 2202
and 2203.
1 = ramp times according to parameters 2205
and 2206.
3)
360 degree grounding under a clamp.
4)
Tightening torque = 0.22 N·m / 2 lbf. in.
5)
Tightening torque = 0.5 N·m / 4.4 lbf. in.
DI3 DI4 Operation (parameter)
0 0 Set speed through
integrated potentiometer
1 0 Speed 1 (1202)
0 1 Speed 2 (1203)
1 1 Speed 3 (1204)