246 Parameters
28.24 Constant frequency
sel3
When bit 0 of parameter 28.21 Constant frequency function is
0 (Separate), selects a source that activates constant
frequency 3.
When bit 0 of parameter 28.21 Constant frequency function is
1 (Packed), this parameter and parameters 28.22 Constant
frequency sel1 and 28.23 Constant frequency sel2 select
three sources that are used to activate constant frequencies.
See table at parameter 28.22 Constant frequency sel1.
For the selections, see parameter 28.22 Constant frequency
sel1.
Always off
28.26 Constant frequency
1
Defines constant frequency 1 (the frequency the motor will
turn when constant frequency 1 is selected).
5.00 Hz
-500.00…500.00
Hz
Constant frequency 1. See par.
46.02
28.27 Constant frequency
2
Defines constant frequency 2. 10.00 Hz
-500.00…500.00
Hz
Constant frequency 2. See par.
46.02
28.28 Constant frequency
3
Defines constant frequency 3. 15.00 Hz
-500.00…500.00
Hz
Constant frequency 3. See par.
46.02
28.29 Constant frequency
4
Defines constant frequency 4. 20.00 Hz
-500.00…500.00
Hz
Constant frequency 4. See par.
46.02
28.30 Constant frequency
5
Defines constant frequency 5. 25.00 Hz
-500.00…500.00
Hz
Constant frequency 5. See par.
46.02
28.31 Constant frequency
6
Defines constant frequency 6. 40.00 Hz
-500.00…500.00
Hz
Constant frequency 6. See par.
46.02
28.32 Constant frequency
7
Defines constant frequency 7. 50.00 Hz
-500.00…500.00
Hz
Constant frequency 7. See par.
46.02
28.41 Frequency ref safe Defines a safe frequency reference value that is used with
supervision functions such as
12.03 AI supervision function
49.05 Communication loss action
50.02
FBA A comm loss func.
0.00 Hz
-500.00…500.00
Hz
Safe frequency reference. See par.
46.02
28.42 Jogging 1
frequency ref
Defines the frequency reference for jogging function 1 in
scalar control mode.
0.00 Hz
-500.00…500.00
Hz
Jogging 1 frequency reference. See par.
46.02
28.43 Jogging 2
frequency ref
Defines the frequency reference for jogging function 2 in
scalar control mode.
0.00 Hz