318 Parameters
45.18 CO2 conversion
factor
Defines a factor for conversion of saved energy into CO
2
emissions (kg/kWh or tn/MWh).
0.500
tn/MWh
(metric ton)
0.000…65.535
tn/MWh
Factor for conversion of saved energy into CO
2
emissions. 1 = 1 tn/MWh
45.19 Comparison power Actual power that the motor absorbs when connected direct-
on-line and operating the application. The value is used for
reference when energy savings are calculated.
Note: The accuracy of the energy savings calculation is
directly dependent on the accuracy of this value. If nothing is
entered here, then the nominal motor power is used by the
calculation, but that may inflate the energy savings reported
as many motors do not absorb nameplate power.
0.00 kW
0.00…10000000.00
kW
Motor power. 1 = 1 kW
45.21 Energy calculations
reset
Resets the savings counter parameters 45.0145.10. Done
Done Reset not requested (normal operation), or reset complete. 0
Reset Reset the savings counter parameters. The value reverts
automatically to Done.
1
45.24 Hourly peak power
value
Value of the peak power during the last hour, that is, the most
recent 60 minutes after the drive has been powered up.
The parameter is updated once every 10 minutes unless the
hourly peak is found in the most recent 10 minutes. In that
case, the values is shown immediately.
0.00 kW
-3000.00 …
3000.00 kW
Peak power value. 10 = 1 kW
45.25 Hourly peak power
time
Time of the peak power value during the last hour. 00:00:00
Time. N/A
45.26 Hourly total energy
(resettable)
Total energy consumption during the last hour, that is, the
most recent 60 minutes.
You can reset the value by setting it to zero.
0.00 kWh
-3000.00 …
3000.00 kWh
Total energy. 10 = 1 kWh
45.27 Daily peak power
value (resettable)
Value of the peak power since midnight of the present day.
You can reset the value by setting it to zero.
0.00 kW
-3000.00 …
3000.00 kW
Peak power value. 10 = 1 kW
45.28 Daily peak power
time
Time of the peak power since midnight of the present day. 00:00:00
Time. N/A
45.29 Daily total energy
(resettable)
Total energy consumption since midnight of the present day.
You can reset the value by setting it to zero.
0.00 kWh
-30000.00
30000.00 kWh
Total energy. 1 = 1 kWh
45.30 Last day total
energy
Total energy consumption during the previous day, that is,
between midnight of the previous day and midnight of the
present day
0.00 kWh
-30000.00
30000.00 kWh
Total energy. 1 = 1 kWh