350 Parameters
76.72 Maximum wear
imbalance
Specifies the maximum wear imbalance, or difference in
running times between any motor, used by the Even wear
setting of parameter 76.70 PFC autochange.
10.00 h
0.00…1000000.00
h
Time. 1 = 1 h
76.73 Autochange level Upper speed limit for the Autochange to occur. The
Autochange occurs when:
• the condition defined in 76.70 PFC autochange is fulfilled
and,
• the speed of the drive motor 01.03 Motor speed % is below
the speed limit defined in this parameter.
Note: When the value is selected as 0%, this speed limit
check is disabled.
100.0%
0.0…300.0% Speed/frequency in percentage of the nominal speed or
frequency of the drive motor.
1 = 1%
76.74 Autochange
auxiliary PFC
Selects whether only auxiliary motors or all motors are
included in the Autochange function.
Aux motors
only
All motors All motors, including the one connected to the drive
participates in the autochange. The Autochange logic will
connect the drive to each of the motors according to setting of
parameter 76.70 PFC autochangee.
Note: The first motor (PFC1) also requires the appropriate
hardware contactor connections and PFC1 must be defined
in one of the relay output source parameters.
0
Aux motors only Only auxiliary (direct-on-line) motors are affected by the
autochange function.
Note: PFC1 refers to the motor that is fixed to the drive and
must not be selected in any of the relay output source
parameters. Only the starting order of the auxiliary motors will
be rotated.
1
76.81 PFC interlock 1 Defines if the PFC motor 1 can be started. An interlocked
PFC motor cannot be started.
0 = Interlocked (not available), 1 = Available.
Available.
PFC motor is
available
Interlocked. PFC
motor is not in use
PFC motor is interlocked and not available. 0
Available. PFC
motor is available
PFC motor is available. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (
10.02 DI delayed status, bit 5). 7
Timed function 1 Bit 0 of 34.01 Timed functions status (see page 273). 8
Timed function 2 Bit 1 of 34.01 Timed functions status (see page 273). 9
Timed function 3 Bit 2 of 34.01 Timed functions status (see page 273). 10
Other [bit] Source selection (see Terms and abbreviations on page 162). -
76.82 PFC interlock 2 See parameter 76.82 PFC interlock 1. Available.
PFC motor is
available
No. Name/Value Description Def/FbEq16